Title
Zero-sequence controller requirements and comparison for a delta-CHB STATCOM under unbalanced operationxmlui.dri2xhtml.METS-1.0.item-contributorOtherinstitution
https://ror.org/000xsnr85https://ror.org/002xeeh02
Version
http://purl.org/coar/version/c_970fb48d4fbd8a85
Rights
© 2024 The AuthorsAccess
http://purl.org/coar/access_right/c_abf2Publisher’s version
https://doi.org/10.1016/j.ijepes.2024.109785Published at
International Journal of Electrical Power & Energy Systems Publisher
ElsevierKeywords
Delta-connected Cascaded H-Bridge (DCHB)
Intercluster power balancing
Resonant controller
Static Synchronous Compensator (STATCOM) ... [+]
Intercluster power balancing
Resonant controller
Static Synchronous Compensator (STATCOM) ... [+]
Delta-connected Cascaded H-Bridge (DCHB)
Intercluster power balancing
Resonant controller
Static Synchronous Compensator (STATCOM)
unbalanced operation
Voltage Source Converter (VSC)
Zero-sequence current [-]
Intercluster power balancing
Resonant controller
Static Synchronous Compensator (STATCOM)
unbalanced operation
Voltage Source Converter (VSC)
Zero-sequence current [-]
xmlui.dri2xhtml.METS-1.0.item-unesco-amplio
http://skos.um.es/unesco6/33xmlui.dri2xhtml.METS-1.0.item-unesco-detallado
http://skos.um.es/unesco6/3306Abstract
Delta-configured Cascaded H-Bridge (DCHB) topology is a suitable alternative for Static Synchronous Compensator (STATCOM) applications. However, under unbalanced voltage and/or current conditions, zer ... [+]
Delta-configured Cascaded H-Bridge (DCHB) topology is a suitable alternative for Static Synchronous Compensator (STATCOM) applications. However, under unbalanced voltage and/or current conditions, zero-sequence current needs to be injected to guarantee dc-link capacitor voltage balancing. The control loop of this zero-sequence current is analyzed in this paper, in order to determine the requirements that the implemented controller must fulfill. Considering these requirements, appropriate transient response and stability margin indicators are defined to quantify and evaluate the performance of different controllers that could be employed —Proportional-Resonant controller (PR), PR controller with delay compensation (PR), and Vector Proportional-Integral controller (VPI) are proposed and analyzed for this application in this paper. Based on the defined indicators, the VPI is the most appropriate among the studied control techniques. Experimental results validate the analytical model of the controllers and their performance. [-]
xmlui.dri2xhtml.METS-1.0.item-oaire-funderName
Gobierno de EspañaGobierno de España
xmlui.dri2xhtml.METS-1.0.item-oaire-fundingStream
Ayudas para la formación de profesorado universitario, en el marco del Plan Estatal de Investigación Científica y Técnica y de Innovación 2017-2020Programa Estatal de Investigación, Desarrollo e Innovación Orientada a los Retos de la Sociedad, en el marco del Plan Estatal de Investigación Científica y Técnica y de Innovación 2013-2016
xmlui.dri2xhtml.METS-1.0.item-oaire-awardNumber
FPU18-04246RTC-2017-26091-3
xmlui.dri2xhtml.METS-1.0.item-oaire-awardURI
Sin informaciónSin información
xmlui.dri2xhtml.METS-1.0.item-oaire-awardTitle
Sin informaciónGrid Ancillary Services Autonomous Converter. GASAC
Collections
- Articles - Engineering [684]
The following license files are associated with this item: